Motortronics :: Digital XLD

Type of Load Three phase AC induction motor
AC Supply Voltage 208 - 600VAC ±10%, 50/60 Hz
HP Ratings 39 - 1250 Amps, 10 - 1125 HP
Unit Overload Capacity
(Percent of motor FLA)
125% - Continuous
500% - 60 seconds
600% - 30 seconds
Power Circuit 6 SCRs
SCR Diode Ratings
(Peak Inverse Voltage)
1600V
Phase Insensitivity Unit operates with any phase sequence
Transient Voltage Protection RC snubber dv/dt networks on each phase.
Cooling Convection up to 180A, fan assisted 62 - 120A,
Fan ventilated 220 - 1250A
Bypass Contactor Shunt rated contactor included as standard in all NEMA 12 enclosed units 92A and above. Also standard with all NEMA 12 combination starters. Line start rated contactor available as an option.
Ambient Condition Design Chassis units: 0¡ to 50 ¡C (32¡ to 122¡F)
Enclosed units: 0¡ to 40¡C (32¡ to 104¡F)
5 - 95% relative humidity
0 - 3300 ft. (1000m) above sea level without derating
Control 2 or 3 wire 120VAC (customer supplied)
Optional 240VAC control voltage and CPTs are available.
Auxiliary Contacts Type / Rating: Form C (SPDT), rated 5 Amps,
240VAC max. (1200VA)
3 Programmable Relays
Fault Indicator: AC triac solid state switch
240VAC, 50mA max.
Approvals UL Listed, Canadian UL (cUL) Listed

Advanced Motor Protection

Two Stage Electronic
Overload Curves
Starting: Programmable for Class 5 through 30
Run: Programmable for Class 5 through 30 when "At-Speed" is detected.
Overload Reset (Note 1) Manual (default) or automatic
Retentive Thermal Memory Overload circuit retains thermal condition of the motor regardless of control power status. Unit uses real time clock to adjust for off time.
Dynamic Reset Capacity Overload will not reset until thermal capacity available in the motor is enough for a successful restart. Starter learns and retains this information by monitoring previous successful starts.
Phase Current Imbalance
Protection (Note1)
Imbalance Trip Level: 5 - 30% current
between any two phases
Imbalance Trip Delay: 1 -20 seconds
OverCurrent
(Electronic Shear Pin)
Protection (Note 1)
Trip Level: 50 - 300% of motor FLA
Trip Delay: 0 - 20 seconds
Load Loss Trip Protection
(Note 1)
Under Current Trip Level: 10 -90 % of motor FLA
Under Current Trip Delay: 0 - 20 seconds
Coast Down (Back Spin)
Lockout Timer (Note 1)
Coast Down Time Range: 1 - 60 minutes
Starts-per-hour Lockout Timer
(Note 1)
Range: 1 - 10 successful starts per hour
Time between starts: 1 - 60 minutes between start attempts

Programmable Outputs

Type / Rating Form C (SPST), Rated 5 amps
240 VAC max, (1200 VA)
Run Indication Start/Stop or Start/End of Decel
At Speed Indication At Speed/Stop or At Speed/End of Decel
Acceleration Adjustments Programmable Ramp Types: Voltage or Current Ramp
(VR or CR)
Starting Torque: 0 - 100% of line voltage (VR)
or 0 - 600% of motor FLA (CR)
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 600% (VR or CR)
Dual Ramp Settings 4 Options: VR1+VR2; VR1+CR2; CR1+CR2; CR1+VR2
Dual Ramp Control: Ramp 1 = Default,
Ramp = 2 selectable via dry contact input
Deceleration Adjustments Begin Decel Level: 0 - 100% of line voltage
Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds
Programmable to decel or coast to stop upon overload trip
Jog Settings
Jog function selected via
dry contact closure input)
Voltage Jog: 0 - 100%
Time of Voltage Jog: 0 - 20 seconds
Current Jog: 100 - 500%
Kick Start Settings
(Note 1)
Kick Voltage: 10 - 100%
Kick Time: 0.1 - 2 seconds
Fault Indications Shorted SCR, Phase Loss, Shunt Trip, Phase Imbalance Trip, Overload, Overtemp, Overcurrent, Short Circuit, Load Loss, or Any Trip
Lockout Indicator Coast Down Time, Starts Per Hour,
Time Between Starts, and Any Lockout

Metering Functions

Phase Currents 0 - 9999 Amps, Phase A, B, or C
Remaining Thermal Capacity 0 - 100% of available motor thermal capacity
Elapsed Time 0 - 1,000,000.0 hours, non resetable
Run Cycle Counter 0 - 10,000,000 run commands, non resetable
Lockout Time Values Remaining time of any enabled lockout timer
Fault Codes Abbreviated fault codes, indicating trip and operating mode
Fault History Last 3 faults with Time and Date Stamps

Serial Communications

Protocol Modbus RTU & RS232
Signal RS-485
Network Up to 247 devices per mode
Functionality Full operation, status view, and programming
via communications port

Operator Interface

LED Readout 4 digit alpha numeric, high brightness, 7 segment display
Keypad 8 functions keys with tactile feedback
Status Indicators 8 LEDs
Remote Mount Capability Up to 10 feet (3 meters) from chassis

Clock and Memory

Operating Memory DRAM loaded from EPROM and EEPROM at initialization
Factory Default Storage Flash EPROM, field replaceable
Customer Settings and Status Non-volatile EEPROM, no battery backup necessary
Real Time Clock Lithium ion battery for clock memory only,
10+ years life span