| Type of Load |
Three phase
AC induction motor |
| AC Supply Voltage |
208 - 600VAC
±10%, 50/60 Hz |
| HP Ratings |
39 - 1250
Amps, 10 - 1125 HP |
Unit Overload Capacity
(Percent of motor FLA) |
125% -
Continuous
500% - 60 seconds
600% - 30 seconds |
| Power Circuit |
6 SCRs |
SCR Diode Ratings
(Peak Inverse Voltage) |
1600V |
| Phase Insensitivity |
Unit operates
with any phase sequence |
| Transient Voltage
Protection |
RC snubber
dv/dt networks on each phase. |
| Cooling |
Convection
up to 180A, fan assisted 62 - 120A,
Fan ventilated 220 - 1250A |
| Bypass Contactor |
Shunt rated
contactor included as standard in all NEMA 12 enclosed units 92A and above.
Also standard with all NEMA 12 combination starters. Line start rated contactor
available as an option. |
| Ambient Condition
Design |
Chassis
units: 0¡ to 50 ¡C (32¡ to 122¡F)
Enclosed units: 0¡ to 40¡C (32¡ to 104¡F)
5 - 95% relative humidity
0 - 3300 ft. (1000m) above sea level without derating |
| Control |
2 or 3
wire 120VAC (customer supplied)
Optional 240VAC control voltage and CPTs are available. |
| Auxiliary Contacts |
Type /
Rating: Form C (SPDT), rated 5 Amps,
240VAC max. (1200VA) |
| 3 Programmable
Relays |
Fault Indicator:
AC triac solid state switch
240VAC, 50mA max. |
| Approvals |
UL Listed,
Canadian UL (cUL) Listed |
Advanced Motor Protection
|
Two Stage Electronic
Overload Curves |
Starting:
Programmable for Class 5 through 30
Run: Programmable for Class 5 through 30 when "At-Speed" is detected. |
| Overload Reset (Note
1) |
Manual
(default) or automatic |
| Retentive Thermal
Memory |
Overload
circuit retains thermal condition of the motor regardless of control power
status. Unit uses real time clock to adjust for off time. |
| Dynamic Reset Capacity |
Overload
will not reset until thermal capacity available in the motor is enough for
a successful restart. Starter learns and retains this information by monitoring
previous successful starts. |
Phase Current Imbalance
Protection (Note1) |
Imbalance
Trip Level: 5 - 30% current
between any two phases
Imbalance Trip Delay: 1 -20 seconds |
OverCurrent
(Electronic Shear Pin)
Protection (Note 1) |
Trip Level:
50 - 300% of motor FLA
Trip Delay: 0 - 20 seconds |
Load Loss Trip Protection
(Note 1) |
Under Current
Trip Level: 10 -90 % of motor FLA
Under Current Trip Delay: 0 - 20 seconds |
Coast Down (Back
Spin)
Lockout Timer (Note 1) |
Coast Down
Time Range: 1 - 60 minutes |
Starts-per-hour
Lockout Timer
(Note 1) |
Range:
1 - 10 successful starts per hour
Time between starts: 1 - 60 minutes between start attempts |
Programmable Outputs
|
| Type / Rating |
Form C
(SPST), Rated 5 amps
240 VAC max, (1200 VA) |
| Run Indication |
Start/Stop
or Start/End of Decel |
| At Speed Indication |
At Speed/Stop
or At Speed/End of Decel |
| Acceleration Adjustments |
Programmable
Ramp Types: Voltage or Current Ramp
(VR or CR)
Starting Torque: 0 - 100% of line voltage (VR)
or 0 - 600% of motor FLA (CR)
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 600% (VR or CR) |
| Dual Ramp Settings |
4 Options:
VR1+VR2; VR1+CR2; CR1+CR2; CR1+VR2
Dual Ramp Control: Ramp 1 = Default,
Ramp = 2 selectable via dry contact input |
| Deceleration Adjustments |
Begin Decel
Level: 0 - 100% of line voltage
Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds
Programmable to decel or coast to stop upon overload trip |
Jog Settings
Jog function selected via
dry contact closure input) |
Voltage
Jog: 0 - 100%
Time of Voltage Jog: 0 - 20 seconds
Current Jog: 100 - 500% |
Kick Start Settings
(Note 1) |
Kick Voltage:
10 - 100%
Kick Time: 0.1 - 2 seconds |
| Fault Indications |
Shorted
SCR, Phase Loss, Shunt Trip, Phase Imbalance Trip, Overload, Overtemp, Overcurrent,
Short Circuit, Load Loss, or Any Trip |
| Lockout Indicator |
Coast Down
Time, Starts Per Hour,
Time Between Starts, and Any Lockout |
Metering Functions
|
| Phase Currents |
0 - 9999
Amps, Phase A, B, or C |
| Remaining Thermal
Capacity |
0 - 100%
of available motor thermal capacity |
| Elapsed Time |
0 - 1,000,000.0
hours, non resetable |
| Run Cycle Counter |
0 - 10,000,000
run commands, non resetable |
| Lockout Time Values |
Remaining
time of any enabled lockout timer |
| Fault Codes |
Abbreviated
fault codes, indicating trip and operating mode |
| Fault History |
Last 3
faults with Time and Date Stamps |
Serial Communications
|
| Protocol |
Modbus
RTU & RS232 |
| Signal |
RS-485 |
| Network |
Up to 247
devices per mode |
| Functionality |
Full operation,
status view, and programming
via communications port |
Operator Interface
|
| LED Readout |
4 digit
alpha numeric, high brightness, 7 segment display |
| Keypad |
8 functions
keys with tactile feedback |
| Status Indicators |
8 LEDs |
| Remote Mount Capability |
Up to 10
feet (3 meters) from chassis |
Clock and Memory
|
| Operating Memory |
DRAM loaded
from EPROM and EEPROM at initialization |
| Factory Default
Storage |
Flash EPROM,
field replaceable |
| Customer Settings
and Status |
Non-volatile
EEPROM, no battery backup necessary |
| Real Time Clock |
Lithium
ion battery for clock memory only,
10+ years life span |