Model
Ratings |
Model
Number
|
Input
Voltage
(+10%/-15%)
|
Output Voltage
|
Motor Rating
|
Rated
Current
(Amps)
|
Rated
Capacity
(kVA)
|
Shipping
Weight
(lbs)
|
|
kW
|
HP
|
|
ME2-1P2-M
|
Single phase
110 - 120V
|
Three phase
200 - 230V
|
0.2
|
1/4
|
1.4
|
0.53
|
1.5
|
|
ME2-1P5-M
|
0.4
|
1/2
|
2.3
|
0.88
|
1.5
|
|
ME2-2P2-M
|
Single phase
200 - 240V
|
0.2
|
1/4
|
1.4
|
0.53
|
1.6
|
|
ME2-2P5-M
|
0.4
|
1/2
|
2.3
|
0.88
|
1.7
|
|
ME2-201-M
|
0.75
|
1
|
4.2
|
1.6
|
1.8
|
|
ME2-202-M
|
Single or Three phase
200 - 240V
|
1.5
|
2
|
7.5
|
2.9
|
3.6
|
|
ME2-203-M
|
2.2
|
3
|
10.5
|
4
|
3.8
|
|
ME2-401-M
|
Three phase
380 - 460V
|
Three phase
380 - 460V
|
0.75
|
1
|
2.3
|
1.7
|
3.5
|
|
ME2-402-M
|
1.5
|
2
|
3.8
|
2.9
|
3.5
|
|
ME2-403-M
|
2.2
|
3
|
5.2
|
4
|
3.6
|
Frequency
Control
|
Frequency
Control Range |
1 - 200Hz |
| Frequency
Resolution |
Digital:
0.1 Hz (0-99.9 Hz), 1 Hz (100 - 200 Hz)
Analog: 1 Hz (60 Hz) |
| Frequency
Setting Signal |
Digital Keypad;
0 - 10VDC, 0-20mA, 10k Potentiometer |
| Frequency
Limit |
Frequency
upper/lower limit |
| Carrier
Frequency |
4 ~ 16 kHz |
|
Control Characteristics
|
Accel/Decel
Time |
0.1 - 999
seconds |
| V/f
Pattern |
6 Patterns |
| Torque
Control |
Manual torque
boost (adjustable) |
| Braking
Torque |
Approximately
20% |
| Multifunction
Inputs |
2 inputs;
emergency stop, pre-set speed, reset, run enable |
| Multifunction
Outputs |
1 (N.O.)
relay for fault, run, up to speed indicator |
| Other
Built-in Functions |
Upper/lower
frequency limit, ramp down or coast to stop, auto reset,
DC injection brake, electronic motor protection |
|
Protective Function
|
Overload |
150% for
1 minute |
| Over-voltage |
ME2-1XX and
ME2-2XX: DC-bus voltage >410VDC
ME2-4XX: DC-bus voltage >815VDC |
| Under-voltage |
ME2-1XX and
ME2-2XX: DC-bus voltage <200VDC
ME2-4XX: DC-bus voltage <400VDC |
| Momentary
Power Loss |
0-2 seconds
(can be restarted via speed search) |
| Stall
prevention |
During accel/decel/constant
speed |
| Output
short circuit |
Provided
by electronic circuit |
| Ground
fault |
Provided
by electronic circuit during start-up and run |
| Other
protection |
Heatsink
fin overtemp, current limit |
| Control Method |
Sinusoidal
wave PWM control (PNP type 12 - 24 VDC) |
| Digital Display |
Indicates
frequency, parameter selection, fault record |
| Ambient temperature |
- 10 to +
50¡ C (14¡ to 122¡ F) |
| Humidity |
95% relative,
non-condensing |
| Vibration |
Under 1G |
| EMC |
Class A filter
standard in all 200 volt units rated 1/4 - 1 HP;
Optional Class B for all other units |
| Enclosure |
Panel Mount
/ IP20 |
| Approvals |
UL, cUL,
CE |
| Mounting |
Direct or
optional DIN rail mount (for drives rated 1 HP and below) |