Motortronics :: Max-L

Type of Load Three phase AC induction motors
AC Supply Voltage 208 - 600VAC ±10%, 50/60 Hz
HP Ratings XLC Soft Start Control:
6 - 180 Amps, 1 - 150 HP
XLS/XLD Soft Starter:
6 - 1250 Amps; 1 - 1125 HP
Unit Overload Capacity
(Percent of motor FLA)
125% - Continuous
500% - 60 seconds
600% - 30 seconds
SCR Peak Inverse Voltage 1600V (consult factory on units rated 39 Amps and below)
Transient Voltage Protection RC snubber dv/dt networks on each phase
Cooling Systems Convection up to 180, fan assisted 62 - 120A,
Fan ventilated 220 - 1250A
Bypass Contactor Shunt rated contactor included as standard in all NEMA 12 enclosed units 92A and above. Also standard with all NEMA 12 combination starters. Line start rated contactor available as an option.
Ambient Condition Design Chassis units: 0¡ to 50 ¡C (32¡ to 122¡F)
Enclosed units: 0¡ to 40¡C (32¡ to 104¡F)
5 - 95% relative humidity
0 - 3300 ft. (1000m) above sea level without derating
Control 2 or 3 wire 120VAC (customer supplied)
Alternate 240 VAC for 380 - 415V
Optional CPTs are available.
Approvals UL and Canadian UL (cUL) listed
Operator Interface XLD: 4 digit alpha-numeric LED display and keypad
XLC/XLS: LED indicators and adjustment potentiometers
Adjustments
Acceleration
Adjustments
Start Voltage 0 - 100% of line voltage
Ramp Time 0 - 60 seconds
Current Limit 200 - 500%
Deceleration Adjustments
(Enabled via dip switch)
Step Down Voltage 0 - 100% of line voltage
Stop Voltage Level 0 - 100% of line voltage
Decel Time 0 - 30 seconds
Motor
and
Soft Start
Protection
Electronic Overload
Relay
XLD: Programmable NEMA Class 5 - 30
XLS: NEMA Class 10 inverse time trip
(Class 20 or 30 optional)
Phase Loss / Imbalance Trips on any phase current less than 30% of nominal unit rating
Phase Rotation Phase sequence insensitive
Shorted Load* Voltage injected during first _ second, looks for current surges at 9x current
Short Circuit* Trips in 12.5ms at 10x unit current rating during run
Shorted SCR* Trips on a voltage drop of less than 1_ V across any SCR pair
Shunt Trip* Separate relay trips on current flow while in the OFF mode (multiple shorted SCRs)
Over Temperature Thermal sensors on heat sinks trip when temperature exceeds 185¼ F
Auxiliary
Contacts
Type / Rating Form C (SPDT), rated 5 Amps,
240VAC max. (1200VA)
Run / Relay Changes state on start/stop command or start/end-of-decel
(if enabled)
Shunt Trip Relay* Changes Power on flow when OFF
Programmable Relay Changes state of Fault or At Speed
Fault Indicator AC triac solid state switch
240VAC, 50mA max
*Units rated 39 amps and above